H05Z1-U/H05Z1-R/H05Z1-K Single core thermoplastic low smoke halogen free polyolefin insulated wire
Application:
Cables suitable for electrical power systems in constructions and other civil engineering buildings, in order to limit fire and smoke production and spread.Suitable for busy transit areas in which it is essential to ensure safety for people, such as: offices, schools, hotels, supermarkets, cinemas, theatres, discotheques, tubes, residential buildings, etc. Recommended for fixed installation in conduits and protected trunking. Also suggested in switchboards, both for distribution and automation systems, due to the presence of particularly fragile equipments and systems towards smoke and corrosive gases.

Construction:
1. Conductor - Solid annealed copper(-U)
- Plain stranded annealed class 2 copper(-R)
- Plain flexible annealed class 5 copper(-K)
2. Insulation - thermoplastic low smoke halogen free polyolefin (TI7)
Cross Section:
1C0.5~1.0mm2
Temperature characteristics:
Conductor operating temperature: -15℃~70℃
Min. temperatrue laying condition: 0℃
Conductor short-circuit operating temperature (5s): 160℃
Minimum Bending Radius
H05Z1-U fixed:6x Outer Ø
H05Z1-R fixed:6x Outer Ø
H05Z1-K Flexible:7.5x Outer Ø fixed:4x Outer Ø
Electrical Characteristics:
Rated voltage: 300/500V
High voltage test: 2.0kV / 5min
Color:
Insulation: According to customer requirements
Standard:
Cable design: EN50525-3-31
Conductor: EN 60228
Flame retardant: IEC60332-1












Our cables are generally packed in wooden drums, steel-wooden drums, or steel drums. For cables of shorter lengths or smaller sizes, coil packaging on pallets is also available.